Tripp Lite SmartPro Line Interactive UPS with enhanced LCD interface offers network-grade power protection for critical server, network and telecommunications equipment. Line Interactive Uninterruptible Power Supply (UPS) with built-in Auto-Voltage Regulation (AVR) actively corrects brownouts and overvoltages back to usable levels while maintaining a full battery charge in case of power failure. Tripp Lite's unique configuration excels in exceptionally poor-power environments with two separate levels of voltage boost to correct both slight undervoltages and severe brownout conditions. Interactive LCD interface reports UPS operating mode, detailed UPS and site-power data, plus enables a variety of UPS setup and configuration options. Super-fast switchover from line to battery power occurs within milliseconds to maintain operation of connected equipment without interruption or reboot. 98% line-mode efficiency offers reduced heat emissions and operating costs. Network management interfaces support communications via USB, RS-232 and optional network management card option. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Network communications ports enable detailed monitoring of equipment load levels, self-test data and utility power conditions. PowerAlert UPS monitoring software is available via free download. Switched output load banks enable scheduled and real-time remote reboot and load shedding of select outlets. Emergency Power Off (EPO) interface. LCD display panel easily rotates for viewing in rackmount or tower configurations. Audible alarm with push-button momentary alarm-cancel and silent-mode configuration options. Programmable self-test. Field-replaceable, hot-swappable battery modules.
OUTPUT
Output Volt Amp Capacity (VA) :2200
Output kVA capacity (kVA) :2.2
Output Watt Capacity (watts) :1600
Output kW capacity:1.6
Output power factor:0.7
Nominal Output Voltage(s) Supported:220V 230V 240V
Nominal Voltage details:230V default (voltage selection via back panel dipswitches)Frequency compatibility:50 / 60 Hz
Output voltage regulation (line mode) :-15%, +8%
Output voltage regulation (Battery mode) :+/- 5%
Built-in UPS output receptacles:8 C13 outlet(s)
Included output power cables:Includes 3 C13 to C14 output power cables
Built-in controllable switched load banks:Three switchable single-outlet C13 load banks
Basic PDU options:PDUNV (1U / 2 C19, 12 C13 outlets)
Switched PDU options:PDUMH15HVNET (1U / 8 C13 outlets)
Output AC waveform (AC mode) :Sine wave
Output AC waveform (battery mode) :Pure Sine wave INPUT
Rated input current (at maximum load) :8.2A (220V), 8.0A (230V), 7.5A (240V)
Nominal Input Voltage(s) Supported:220V AC 230V AC 240V AC
UPS input connection type:C20 inlet
UPS input connection description:IEC320-C20 input connection accepts a variety of detachable cordsets to match country or site-specific wall receptacles
Input circuit breaker15A BATTERY
Full load runtime (minutes) :6 min. (1600w)
Half load runtime (minutes) :17 min. (800w)
Expandable battery runtime:Extended runtime supported via optional external battery packs
External battery pack compatibility:BP48V24-2U (limit 1) BP48V60RT3U (multi-pack compatible)
DC system voltage (VDC) :48
Battery recharge rate (included batteries) :Less than 4.5 hours from 10% to 90%
Replacement battery cartridge (internal UPS battery replacement) :RBC94-2U
Battery Access:Front panel battery access door
Battery replacement description:Hot-swappable, user replaceable batteries VOLTAGE REGULATION
Voltage regulation description:Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 158 to 290
Overvoltage correction:Voltage reduction of 12% applies when input is between 232-266V (220V), 244-278V (230V) or 254-282V (240V)
Undervoltage correction:Voltage boost of 12% applies when input voltage is between 174-198V (220V), 183-206V (230V) or 191-216
Severe undervoltage correction:Voltage boost of 24% applies when input voltage is between 158-206V (230V) or 166-190V (240V) LEDS ALARMS and SWITCHES
LED Indicators:5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Alarms:Audible alarm indicates power-failure, overload and low-battery conditions
Alarm cancel operation:Power-fail alarm can be silenced using alarm-cancel switch once silenced, alarm will re-sound to indicate low-battery status
Switches:2 Switches control off/on power status and alarm-cancel/self-test operation rear panel protected switches support low/high charger settings SURGE / NOISE SUPPRESSION
UPS AC suppression joule rating:350
UPS AC suppression response time:Instantaneous
EMI / RFI AC noise suppression:Yes COMMUNICATIONS
Communications interface:USB (HID enabled) DB9 Serial EPO (emergency power off) Slot for SNMP/Web interface
Network monitoring port description:Supports detailed monitoring of UPS and site power conditions
PowerAlert software:Included
Communications cable:USB and DB9 cabling included
WatchDog compatibility:Supports Watchdog application, OS and hard-reboot restart options for remote applications LINE / BATTERY TRANSFER
Transfer time:2-4 milliseconds
Low voltage transfer to battery power (setpoint) :174V (220V), 158V, (230V), 166V (240V)
High voltage transfer to battery power (setpoint) :266V (220V), 278V (230V), 290 V (240V) CERTIFICATIONS
UPS Certifications:Tested to CE (EU) Tested to GOST (Russia) Tested to SASO (Saudi Arabia) Meets FCC Part 15 Category A (EMI)
UPS Certification details:CE / IEC 62040, TUV with GS mark Item Dimension (L"xW"xH") : 20 x 23.5 x 9
Dimensional Weight :72.0 lb Warranty Information :
2 years
Tripp Lite SmartPro 2200VA 1600W 230V Tower Rack-mountable 2U UPS SMX2200XLRT2U