OUTPUT
Output Volt Amp Capacity (VA): 2200
Output kVA capacity (kVA): 2.2
Output Watt Capacity (watts): 1920
Output kW capacity: 1.92
Output power factor: 0.87
Output Capacity Details: Output de-rates to 1800w at 110V and 1670w at 100V nominal settings
Nominal Output Voltage(s) Supported: 100V 110V 120V
Nominal Voltage details: 120V default (voltage selection via back panel dipswitches)
Frequency compatibility :50 / 60 Hz
Frequency compatibility details: Supports 60Hz at 110V and 120V nominal and 50/60Hz (auto-sensing) at 100V nominal.
Output voltage regulation (line mode): -14%, +6%
Output voltage regulation (Battery mode): +/- 5%
Built-in UPS output receptacles: 4 x 5-15R outlet(s) 4 x 5-15/20R outlet(s)
Built-in controllable switched load banks: Three switchable single-outlet 5-15R load banks
Basic PDU options: PDU1220 (1U / 13 5-15/20R outlets) PDUNV (1U / 2 C19, 12 C13 outlets) PDUV20 (0U / 12 5-15/20R outlets) PDU40TDUAL (0U / 40 5-15/20R outlets)
Metered PDU options: PDUMH20 (1U / 13 5-15/20R outlets) PDUMH20AT (1U / 16 5-15/20R outlets) PDUMV20 (0U / 16 5-15/20R outlets) PDUMV40 (0U / 32 5-15/20R outlets)
Switched PDU options: PDUMH20ATNET (1U / 16 5-15/20R outlets) PDUMV20NET (0U / 24 5-15/20R outlets)
External PDU redundancy options: Auto Transfer Switch features utilizing the secondary PDU input cord are compatible with Smart Online UPS models only
Output AC waveform (AC mode): Sine wave
Output AC waveform (battery mode): Sine wave
INPUT
Rated input current (at maximum load) :16A (120V), 16.4A (110V), 16.7A (100V)
Nominal Input Voltage(s) Supported :100V AC 110V AC 120V AC
UPS input connection type: 5-20P
Input circuit breake:r 20A
UPS Input cord length (ft.): 10
UPS Input cord length (m) :3
Recommended Electrical Service :20A 120V
BATTERY
Full load runtime (minutes): 5 min. (1920w)
Half load runtime (minutes): 13 min. (960w)
DC system voltage (VDC): 48
Battery recharge rate (included batteries) :Less than 4.5 hours from 10% to 90%
Replacement battery cartridge (internal UPS battery replacement): RBC94-2U
Battery Access: Front panel battery access door
Battery replacement description :Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation description: Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Overvoltage correction: Voltage reduction of 12% applies when input is between 127 and 145 (120V), 116 and 133 (110V), 106 and 121 (100V)
Undervoltage correction: Voltage boost of 12% applies when input voltage is between 96 and 108 (120V), 87 and 99 (110V), 83 and 90 (100V)
Severe undervoltage correction: Voltage boost of 24% applies when input voltage is between 83 and 95 (120V only)
LEDS ALARMS SWITCHES
LED Indicators: 5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Alarms: Audible alarm indicates power-failure, overload and low-battery conditions
Alarm cancel operation: Power-fail alarm can be silenced using alarm-cancel switch once silenced, alarm will re-sound to indicate low-battery status
Switches: 2 Switches control off/on power status and alarm-cancel/self-test operation rear panel protected switches support nominal voltage selection
SURGE / NOISE SUPPRESSION
UPS AC suppression joule rating: 570
UPS AC suppression response time: Instantaneous
EMI / RFI AC noise suppression :Yes
PHYSICAL
Installation form factors supported with included accessories: 4 post 19 inch rackmount (mounting rail kit included)
Installation form factors supported with optional accessories: 2 post rackmount (2POSTRMKITWM) Wallmount (2POSTRMKITWM) Tower (2-9USTAND)
Primary form factor: Rackmount
UPS / Power Module dimensions in primary form factor (height x width x depth / inches): 3.5 x 17.5 x 19
UPS / Power Module dimensions in primary form factor (height x width x depth / cm) :8.9 x 44.4 x 48.3
Installed whole system total rack space height (rack spaces): 2U
Secondary form factor: Tower (requires 2-9USTAND)
Installed whole system dimensions in secondary form factor (height x width x depth / inches): 17.5 x 3.5 x 19
UPS dimensions in secondary form factor (height x width x depth / cm): 44.4 x 8.9 x 48.3
UPS / Power Module weight (lbs) :64
UPS / Power Module weight (kg): 29.1
UPS Shipping dimensions (height x width x depth / inches): 9 x 23.5 x 20
UPS Shipping dimensions (height x width x depth / cm) :22.9 x 59.7 x 50.8
Shipping weight (lbs) :72
Shipping weight (kg) :32.7
UPS housing material :Steel
Cooling method :Fan
COMMUNICATIONS
Communications interface: USB (HID enabled) DB9 Serial EPO (emergency power off) Slot for SNMP/Web interface
Network monitoring port description :Supports detailed monitoring of UPS and site power conditions
PowerAlert software: Included
Communications cable: USB and DB9 cabling included
WatchDog compatibility: Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer time :2-4 milliseconds
Low voltage transfer to battery power (setpoint) :83 (120V), 87 (110V), 83 (100V)
High voltage transfer to battery power (setpoint): 145 (120V), 133 (110V), 121 (100V)
CERTIFICATIONS
UPS Certifications :Tested to UL1778 (USA) Tested to CSA (Canada) Tested to NOM (Mexico) Meets FCC Part 15 Category A (EMI) ROHS (Reduction of Hazardous Substances)
Tripp Lite, UPS, SmartPro 2200VA, 120V, 1920, 2U, AVR, 4 x 5-15R, 4 x 5-15/20R, USB, DB9, EPO