The Tripp Lite PDUH20HVL6 PDU L6-20P Horizontal Outlet is rack mountable for your convenience. It supports four front-facing and 10 rear-facing outlets. This 208v Tripp Lite PDU features reversible housing that enables both front or rear input cable entry.
OVERVIEW
PDU Type:Basic
OUTPUT
Output Capacity Details:3.84kW (240V), 3.33kW (208V), 3.2kW (200V) / 20A total capacity (Agency de-rated 16A) 16A max per C19 outlet 12A max per C13 outlet
Frequency Compatibility:50 / 60 Hz
Output Receptacles:(12) C13 (2) C19
Output Nominal Voltage:200 208 240
Overload Protection:n/a
INPUT
PDU Input Voltage:200 208 240
Recommended Electrical Service:20A 208/240V
Maximum Input Amps:20
Maximum Input Amps Details:Agency de-rated to 16A continuous
PDU Plug Type:NEMA L6-20P
Input Cord Details:Input cable is attached
Input Cord Length (m):4.57
Input Phase:Single-Phase
USER INTERFACE, ALERTS CONTROLS
Switches:n/a
PHYSICAL
Minimum Required Rack Depth (cm):17.27
Shipping Dimensions (hwd / cm):5.7 x 52.1 x 24.1
Shipping Weight (kg):2.7
Unit Dimensions (hwd / cm):4.45 x 43.8 x 9.5
Unit Weight (kg):1.70
Material of Construction:Metal
Form Factors Supported:1U rackmount, 0U vertical rackmount, wall-mount, and under-counter installation
PDU Form Factor:1U Horizontal
Outlets Measurement (Center to Center):Distance between front (C13) outlets 28.75mm Distance between rear (C19) outlets 55mm Distance between rear (C13) outlets 28.75mm
Minimum Required Rack Depth (mm):173
ENVIRONMENTAL
Storage Temperature Range:5 to 122F (-15 to 50C)
Relative Humidity:5 to 95% non-condensing
Operating Elevation (ft.):0-10,000
Operating Elevation (m):0-3000
SPECIAL FEATURES
TVSS Grounding:Rear grounding lug
CERTIFICATIONS
Certifications:Tested to UL 60950 (USA), CSA (Canada), RoHS Compliant
Item Dimension (L inchxW inchxH inch)
10 x 21 x 3 Weight
5.90lb Warranty Information
5-year limited warranty